What is the maximum slope for a ramp in an existing business occupancy?
What is the maximum slope for a ramp in an existing business occupancy?A . 1 in 8B . 1 in 10C . 1 in 12D . 1 in 14View AnswerAnswer: C Explanation: The maximum allowable slope for ramps in existing buildings, including business occupancies, is specified in NFPA 101®, Life...
Which of the following statements is true regarding combustible materials used in the playground structure's construction?
A fire inspector is inspecting a fast-food restaurant that has an indoor playground structure exceeding 10 ft (3.1 m) in height and 160 ft³ (14.9 m²) in area. Which of the following statements is true regarding combustible materials used in the playground structure's construction?A . Combustible materials are not permittedB...
Which of the following is true regarding the copy of an issued permit?
Which of the following is true regarding the copy of an issued permit?A . It shall be readily accessible at each place of operation.B . It shall be reissued upon completion of the project.C . It shall be maintained by the architect of record.D . It shall be transferable to...
What is the minimum acceptable flow at the base of the riser for a pipe-schedule sprinkler system in an ordinary hazard (Group 1) occupancy?
What is the minimum acceptable flow at the base of the riser for a pipe-schedule sprinkler system in an ordinary hazard (Group 1) occupancy?A . 250 gpm (946 L/min)B . 500 gpm (1,893 L/min)C . 700 gpm (2,649 L/min)D . 850 gpm (3,218 L/min)View AnswerAnswer: B Explanation: For a pipe-schedule...
For flammable and combustible liquids, what is the number of control areas allowed on the 2nd floor above grade level of a building?
For flammable and combustible liquids, what is the number of control areas allowed on the 2nd floor above grade level of a building?A . 2B . 3C . 4D . 5View AnswerAnswer: B Explanation: The number of control areas for flammable and combustible liquids is regulated under NFPA 30 and...
Which of the following conditions must be considered when determining the spacing and location of smoke detectors?
Which of the following conditions must be considered when determining the spacing and location of smoke detectors? I. Ceiling height II. Detector sensitivity III. Ambient environment IV. Ventilation or airflowA . I and IVB . II and IIIC . I, III, and IVD . I, II, III, and IVView AnswerAnswer:...
At what minimum pressure would automatic sprinkler piping be hydrostatically tested if the maximum system pressure is 175 psi (12 bar)?
At what minimum pressure would automatic sprinkler piping be hydrostatically tested if the maximum system pressure is 175 psi (12 bar)?A . 175 psi (12 bar)B . 200 psi (13.8 bar)C . 225 psi (15.5 bar)D . 250 psi (17 bar)View AnswerAnswer: B Explanation: According to NFPA 13, Standard for...
What is the color of the glass bulb in a 155°F (66°C) temperature-rated sprinkler head?
What is the color of the glass bulb in a 155°F (66°C) temperature-rated sprinkler head?A . Orange or redB . Yellow or greenC . BlueD . PurpleView AnswerAnswer: A Explanation: The color of the glass bulb in sprinkler heads indicates the temperature rating at which the bulb will activate. These...
After conducting the annual test of a dry barrel hydrant, what is the maximum length of time permitted for full drainage to take place?
After conducting the annual test of a dry barrel hydrant, what is the maximum length of time permitted for full drainage to take place?A . 10 minutesB . 15 minutesC . 30 minutesD . 60 minutesView AnswerAnswer: B Explanation: Dry barrel hydrants must be tested annually to ensure proper drainage...
In occupancies where a Class A or Class B interior finish is required, which of the following is the allowable amount of Class C materials?
In occupancies where a Class A or Class B interior finish is required, which of the following is the allowable amount of Class C materials?A . 5 percentB . 10 percentC . 15 percentD . 20 percentView AnswerAnswer: B Explanation: The use of interior finish materials is regulated by NFPA...