In new health care occupancies, unattended soiled linen receptacles that exceed the permitted capacity must be located in which one of the following locations?

In new health care occupancies, unattended soiled linen receptacles that exceed the permitted capacity must be located in which one of the following locations?
A . Corridor
B . Nurses station
C . Hazardous area
D . Patient room

Answer: C

Explanation:

In health care occupancies, soiled linen receptacles pose a fire and contamination risk if they exceed allowable capacity. According to NFPA 101®, Life Safety Code®, Section 18.7.5.7:

Soiled linen receptacles exceeding 32 gallons (121 liters) in capacity must be stored in a hazardous area (C).

A hazardous area is a space specifically designed with fire-rated enclosures and safety measures to contain risks associated with combustible materials.

Corridor (A): Storing large soiled linen containers in corridors is prohibited to ensure clear egress pathways.

Nurses station (B) and Patient room (D): These are not designated hazardous areas and are inappropriate for storing excessive amounts of soiled linens.

Reference: NFPA 101, Section 18.7.5.7: Storage and location requirements for soiled linen and trash receptacles.