How should you proceed with the placement of your cables?

You are required by architectural design to place UTP cables in the same space as unshielded power lines.

How should you proceed with the placement of your cables?
A . Require the architect/electrical engineer to place shielding in the space before your UTP is placed.
B . You should provide a minimum separation of 610 mm (24 in).
C . You should provide a minimum separation of 229 mm (9 in).
D . You should provide a minimum of two 101 mm (4 in) RM

Answer: B

Which of the following is NOT true about consolidation points?

Which of the following is NOT true about consolidation points?
A . They are not to be used for direct connections to active equipment.
B . They allow horizontal cables to be extended into work area pathways.
C . They are to be terminated on separate connectors for each individual user.
D . The maximum length of cable from the consolidation point (CP) to the outlet varies by media type.

Answer: D

When specifying telecommunications outlet boxes, all of the following should be considered EXCEPT:

When specifying telecommunications outlet boxes, all of the following should be considered EXCEPT:
A . Outlet box shall be a minimum of 100 mm (4 in) x 100 mm (4 in) x 76 mm (3 in)
B . Outlet boxes should be installed near an electric outlet at the same height
C . Different outlet boxes have different support requirements
D . Floor mounted telecom outlet boxes should be coordinated with furniture to minimize the potential trip hazard
E . Outlet boxes must be of adequate size so that minimum cable bend radius requirements are not exceeded

Answer: A